Definition
3.1 – ALARM CONDITION
ü
One consideration was the fact that an ALARM SYSTEM might generate ALARM SIGNALS for an ALARM CONDITION when no valid ALARM CONDITION existed (i.e. a FALSE POSITIVE ALARM CONDITION). A second was the issue that non-numerical values or conditions,
or the use of an INTELLIGENT ALARM SYSTEM, might be used to determine the presence of an ALARM CONDITION, yet these factors
might not have been included in previous definitions of ALARM LIMIT.
ü
On this basis, the committee defined ALARM CONDITION as: “state of the ALARM SYSTEM when it has determined
that a potential or actual HAZARD exists.” This definition recognizes that the ALARM SYSTEM can be correct or
incorrect in its determination. It also indicates that this state will cause
the ALARM SYSTEM, if it is enabled, to generate ALARM SIGNALS for the ALARM CONDITION to bring about OPERATOR response or awareness.
ü
The committee then defined ALARM LIMIT as: “threshold used by
an ALARM SYSTEM to determine an ALARM CONDITION.” The obvious example would be a numerical threshold (such as a
threshold for a high heart rate ALARM
CONDITION), but some thresholds
might be nonnumerical. Non-numerical conditions, such
as a switch in the incorrect position, failure of the OPERATOR to enter certain data or
the failure of the ALARM SYSTEM, can also cause an ALARM
CONDITION. Furthermore, an INTELLIGENT ALARM SYSTEM can be
used to determine an ALARM CONDITION, using an algorithm rather than a simple threshold value. Such an
algorithm may have multiple inputs, perform logic-based or time-dependent
averaging, use intelligent artefact filtering or
employ other techniques so that the actual threshold changes over time or in
response to other circumstances.